On May 2, 2024, a hailstorm with 50–60 mm hail crossed the Anson 1 solar plant near Abilene, Texas, causing severe damage and requiring over 12,000 modules to be remediated [1]. From May–December 2024, the 200 MW site produced about 55% less energy than in the same months of other years. Using data available via the EnergyStream API, we estimate lost energy due to the storm at 194–253 GWh, worth roughly $4.0–5.3 million.
Around 6:00 PM local time on May 2, 2024, a hailstorm with approximately 50–60 mm hail stones crossed over the Anson 1 solar site near Abilene, TX. The interactive map below shows the path of the hail swath as it moved, with the outline of the Anson site highlighted. The hail data shown here is derived directly from NOAA's MRMS Mesh product.
According to various filings for the installation submitted from 2019 through 2024, the Anson 1 solar facility is a 200 MW installation with the following equipment specifications:
Please note that these are self-reported module manufacturer and model specifications in permit filings, and may differ from the actual module numbers/manufacturer/model on site.
The tempered glass thickness for both the Astronergy and VSUN modules is 3.2 mm, much thicker than many modern module technologies at only 2 mm. Modules with these specs are frequently more robust during hailstorms [2]. However, in the case of catastrophic hail events (hail generally exceeding 40–50 mm in diameter), significant damage can still occur.
Table 1 shows all weather-related outages at the Anson site from May 2024 through December 2024. These outages are labeled as ice/cold weather events — normally assigned to winter events in Texas, but occasionally also assigned to extreme hail events that cause system outages. In total, there were approximately 8,697 unit-hours (summed across both units) of downtime likely associated with hail damage from the May 2024 storm, including partial and full outages, running intermittently from May through December as module replacement and remediation efforts were scheduled.
| Period (local, CT) | Duration | Curtailed | Outage type | ERCOT reason code |
|---|---|---|---|---|
| May 2 – May 31 | 29.7 days | 57 MW (57%) | FORCED | COLD WEATHER RELATED* |
| Aug 1 – Aug 25/30 | 24–30 days | 61 MW (61%) | FORCED | COLD WEATHER RELATED* |
| Aug 25 – Aug 30 (Unit 1) | 5.6 days | 91 MW (91%) | FORCED | COLD WEATHER RELATED* |
| Sep 1 – Sep 30 | 30.0 days | 61 MW (61%) | FORCED EXTENSION | COLD WEATHER RELATED* |
| Oct 1 – Nov 19 | 49.6 days | 10 MW (10%) | FORCED | COLD WEATHER RELATED* |
| Nov 19 – Dec 31 | 42.2 days | 50 MW (50%) | FORCED | COLD WEATHER RELATED* |
Figure 2 illustrates the unit-level impact of the storm on the Anson site. Original unit-level AC energy data is available at 15-minute intervals, but it is summed to daily rollups for easier viewing here. During this period, production for both units dropped by approximately 55% compared to average production during the same months in other years (2021, 2022, 2023, 2025).
Using overall outage dates assigned to the "ice/cold weather" category and actual production during these periods, we can develop a basic methodology to estimate production losses as a result of the hail event. Note that this does not account for equipment losses or remediation costs. We are also attributing all lost production during the extended outage period of May to December to hail losses; there may be lost production due to other reasons that we are unaware of. Outage records for Anson between May–December 2024 do include some minor outages for maintenance reasons, but the majority of outages are attributed to hail damage.
To approximate the overall cost of the outage, we use solar satellite data to estimate the "ideal" unit-level production for all solar units experiencing an outage. This data, pulled from the National Laboratory of the Rockies' (formerly NREL) National Solar Radiation Database (NSRDB) [3], is fed into a PVWatts simulation to estimate production based on solar satellite irradiance [4]. Inputs include manually audited solar metadata available via the EnergyStream solar plant details endpoint. Excluding the weather-related outages, average production runs around 85% of idealized modeled production; during the outage event, actual production drops to approximately 37% of idealized production.
Now that we know what the installation would have produced under ideal conditions, we can subtract actual production from idealized production during the listed hail outage period to estimate maximum lost energy:
total lost energy, MWh = max((PVWatts energy, MWh − actual energy, MWh), 0)
We set a clipped value of 0 when actual production is higher than ideal production, which can happen occasionally. Using this equation, we estimate a total lost energy of approximately 253 GWh across both Anson units. This value acts as a maximum threshold, as it assumes Anson would have produced at its "idealized" PVWatts-modeled level if not hit by the hailstorm.
Given that Anson produced about 85% of idealized production in the years without hail damage, we can also compare actual production against 85% of idealized production at each 15-minute interval:
lost energy, MWh = max((0.85 × PVWatts energy, MWh − actual energy, MWh), 0)
This gives a lower threshold of approximately 194 GWh.
Now that we have total energy lost, we can take this calculation further by estimating the total cost of the lost energy, using 15-minute settlement point pricing data associated with Anson. To do this, we simply multiply our 15-minute lost energy values with 15-minute settlement point price data, and then sum over the entire outage period to get the max total cost of lost production:
total loss, $ = Σ total lost energy, MWh × settlement point price
Using the equation above, the max total production loss due to the hailstorm was approximately $5.3 million. Given this assumes idealized energy, we can once again use the 85% adjustment, setting a lower threshold of $4.0 million. Given these numbers, we estimate the overall production losses at Anson due to the hailstorm were between $4.0 and $5.3 million.
This methodology shows how much a catastrophic hailstorm can cost in downtime for an impacted solar site. In the case of Anson 1, the May 2024 hailstorm led to 194–253 GWh of lost energy, or roughly $4.0–5.3 million at settlement point prices. These figures are modeled estimates, not metered losses: they rely on self-reported equipment details from permit filings, on outages coded by the grid operator as cold-weather events and attributed to hail based on timing, and on a modeled "ideal" production baseline. Actual losses will also depend on factors such as insurance terms, power purchase agreements, and hedges.
Implementing tracker hail stow systems, available from companies like Nextracker, Array Technologies, and FTC Solar, can mitigate damage to utility solar installations. By implementing hail stow during a storm, damages can be reduced significantly, and situations like Anson's can be heavily avoided. Furthermore, using hail stow trackers in high-risk areas can drop insurance premiums significantly.
This analysis relies on data available in the EnergyStream API. Datasets used are provided via the links below. If you're interested in learning more about the EnergyStream API, check out our API reference or request a demo. Free accounts get 100 queries a month on select endpoints, including weather risk profiles for 18,000 utility sites across the United States and site metadata details. Professional and Enterprise accounts get full access to production data for over 700 sites going back to 2014, as well as outage data for over 1,600 sites across Texas and California going back to 2020.